    The EL2904 TwinSAFE component is a digital output terminal
    with four channels.
    It switches 24 V DC actuators up to 0.
    5 A per channel and has four fail-safe outputs
    .
    The output is controlled
    by a component with TwinSAFE logic via FSoE.
    If an error is detected (failure stop), the component shuts down
    automatically.
    The EL2904 has safety parameters that allow functions to be specially adapted to the respective safety requirements
    .
    For example, current measurement and output test at the output can be configured to be able to detect cross-circuits and react
    appropriately.
    In addition, standard output
    can be activated for the EL2904.
    Therefore, the corresponding standard output can be paralleled in the process image with the safe output of the EL2904 and "AND" performed internally
    .
    The safe output signal controlled by TwinSAFE Logic thus emits a safe release as a standard signal, which can be triggered by a non-safety-oriented control system, independent of the safety controller and the FSoE cycle
    .
    This allows for faster output switching times, provided that the safety controller issues the necessary release
    for the output.
    Security parameters are not stored directly on the component, but are transferred to the component through the component
    with the TwinSAFE Logic function when the security application is launched.
    This simplifies the service procedure, as components
    can be simply replaced.
    When the security application is restarted, the safety-related parameters are transferred to the new component
    .
    Special features: 4 safety outputsIntegrated current measurementCan activate channel testingStandard outputActivation of productsInformation technology data accessoriesSoftware documentation and download media libraryMore information related productsTechnical dataHousing data reaching the apex technical dataEL2904 connection technology1-/2-wire specification output signalThe number of output outputs4 maximum
    。 Output current 0.
    5 A (per channel), min.
    20 mA (active current measurement) protocol TwinSAFE/EtherCAT safe fault response time≤ Watchdog time (parameterizable) Current consumptionPower supply contact load-dependent current consumption E-bus type
    。 Safety standards for 221 mA installation position level DIN EN ISO 13849-1:2008 (Class 4, PL e) and EN 61508: 2010 (SIL 3) Weight approx.
    100 g IP protection class IP20 explosion protection mark II 3 G Ex nA IIC T4 Gc Technical data Housing data to the apex Housing data EL-24-2x8pin Design form compact terminal housing material with signal LED polycarbonate dimensions (W x H x D) 24 mm x 100 mm x 68 mm mounted on 35 mm DIN rail according to EN 60715 Label wiring solid conductors (e), flexible conductors (f) and ferrules (a) of the BZxxx series marked with lock by side-by-side installation of double grooves and key connections BZxxx series: screwdriver driven spring connection section s*: 0.
    08.
    .
    .
    2.
    5 mm²,st*: 0.
    08.
    .
    .
    2.
    5 mm²,f*: 0.
    14.
    .
    .
    1.
    5 mm² connection cross-section AWGs*: AWG 28.
    .
    .
    14,st*:AWG 28.
    .
    .
    14,f*:AWG 26.
    .
    .
    16 stripping length 8.
    .
    .
    9 mm current load power contact I max: 10 A*s: solid wire; st: stranded wire; f: With ferrule
    This article is an English version of an article which is originally in the Chinese language on echemi.com and is provided for information purposes only. This website makes no representation or warranty of any kind, either expressed or implied, as to the accuracy, completeness ownership or reliability of the article or any translations thereof. If you have any concerns or complaints relating to the article, please send an email, providing a detailed description of the concern or complaint, to service@echemi.com. A staff member will contact you within 5 working days. Once verified, infringing content will be removed immediately.